Function
To control the PV inverter, the easYgen3000XT calculates (based on the generator real load and the generator minimum load):
- The AM variable 10.39 PV load ref. [%] (PV set-point value 0% – 100%)
The regulation output (analog or in steps) is treated as follows:
- If the Function is disabled, the output 10.39 PV load ref.[%] is 0%.
- If the Function is enabled and LM ”Release PV regulation“ is FALSE, the output 10.39 PV load ref. [%] is 100%.
- If the Function is enabled and LM ”Release PV regulation“ is TRUE, the output 10.39 PV load ref. [%] shows the
current PID value and the corresponding LM “PV load ref.” is TRUE.